Advent Commercial Fire
Advent Fire delivers advanced hardwire/wireless fire protection for both new and existing commercial fire alarm installations. Advent Fire is easy to install and simple to use.
Advent Fire is suited for large applications or where future expansion may be required.
Part no: 60-562-03 (250 Zones, 8 Partitions)
Part no: 60-562-06 (132 Zones, 4 Partitions)
Advent Fire delivers advanced hardwire/wireless fire protection for both new and existing commercial fire alarm installations. Advent Fire is easy to install and simple to use.
The system is available in two models:
- 60-562-03 has 250 zones, 8 partitions, and up to 250 users
- 60-562-06 has 132 zones, 4 partitions, and up to 100 users
Advent Fire is suited for large applications or where future expansion may be required.
Standard Features
- Six general purpose inputs/outputs, one 12 VDC 2-wire smoke loop, one general purpose input only zone
- Supports up to 132 or 250 supervised, fire-rated hardwire zones (depending on model)
- Supports a maximum of 132 wireless zones (both models)
- 78 pre-defined zone configuration types
- 4 or 8 partitions (based on model)-two account numbers per partition; 32 shared schedules per partition
- 100 or 250 user-programmable access codes (based on model); 4.6 digit lengths allowed
- 800 word vocabulary for voice and display
- 12 VDC, 5 amp auxiliary power output
- On- and off-site telephone access with digitized-voice feedback
- Dual SuperBus Ports-support up to 62 bus devices (31 per port)
- 2,048 event buffer with time and date stamp
- Contact ID™ reporting format
- Up to 16 alphanumeric pagers or cellular phones with paging capability
- Long Range Radio (LORRA); pre-programmed, on-board header
- Network buddy system
- Programming can be downloaded using ITI Advent Downloader
- Flash memory, downloadable upgrades
Specifications
Power Supply:
| Required Transformer | Class I Single Internal 24 VAC, 100 VA |
| Backup Battery | 12 VDC, 17.2 - 18.0 Ah rechargeable, sealed, lead-acid (up to 3—additional enclosure required for third battery) |
| Battery Backup Time | Minimum 24 hours (based on load and number of backup batteries installed) |
| Battery Test | Every 4 hours (default) or 24 hours |
| Fuse | 12 VDC, 5-amp built-in current limiting circuitry: SuperBus outputs limited to 650 mA each, long-range radio output limited to 250 mA |
Telephone/Modem:
| Dialing | DTMF or pulse |
| Modem | Up to 14,400 bps, Bell 103, Bell 212A, V.32bis, V.32, V.22bis, V.22, V.23, V.21, V.42bis |
| Telephone Interface | Line seizure relay, DTMF phone control, line supervision |
| Color: | Fire Red |
| Dimensions: | 21.5" wide, 14.75" high, 5.0" deep |
Approvals
- FCC Parts 15 and 68
- UL 365: Police Station Connected Burglar Alarm Units and Systems
- UL 609: Local Burglar Alarm Units and System
- UL 864: Control Units for Fire Protective Signaling Systems
- Local Non-Coded Fire Alarm Systems
- Auxiliary Fire Alarm Systems
- Central Station Fire Alarm Systems—DACT
- Remote Station Fire Alarm Systems—DACT
- Protected Premise Fire Alarm Systems—DACT
- Type of Service: Automatic Fire Alarm, Manual Fire Alarm, Waterflow Alarm
- UL 985: Household Fire Warning System Units
- UL 1023: Household Burglar Alarm System Units
- UL 1610: Central-Station Burglar Alarm System Units
- UL 1635: Digital Alarm Communicator Systems
- UL 1637: Home Health Care Signaling Equipment
- CSFM California State Fire Marshall
- Complies with NFPA 72 Fire Alarm Code